Troubleshooting
|
Step |
Action |
Yes |
No |
| 1 | Check accessories which use excessive amounts of
electricity. Are accessories being installed? |
Remove accessories. | Go to step 2. |
| 2 | Check the battery for current leakage. Refer to “battery
current leakage inspection” . Is the battery for current leakage ok? |
Go to step 3. |
|
| 3 | Measure the regulated voltage between the battery
terminals. Refer to “regulated voltage inspection” (page 1j-
3). Is the regulated voltage ok? |
|
Go to step 4. |
| 4 | Measure the resistance of the generator coil. Refer to “generator
inspection” . Is the resistance of generator coil ok? |
Go to step 5. |
|
| 5 | Measure the generator no-load performance. Refer to “generator
inspection” . Is the generator no-load performance ok? |
Go to step 6. | Faulty generator |
| 6 | Inspect the regulator/rectifier. Refer to “regulator / rectifier
inspection” . Is the regulator/rectifier ok? |
Go to step 7. | Faulty regulator/rectifier |
| 7 | Inspect wirings. Is the wirings ok? |
Faulty battery. |
|
Charging system symptom diagnosisFront brake master cylinder parts inspection
Refer to “front brake master cylinder / brake lever disassembly and assembly”
.
Master cylinder
Inspect the master cylinder bore for any scratches or
other damage
Piston / rubber parts
Inspect the piston surface for any scratches or other
damage.
Inspect the primary cup, secondary cup ...
Throttle cable removal and installation
Removal
Remove the air cleaner box. Refer to “air cleaner box removal and
installation” .
Remove the right handlebar switch box. Refer to “handlebar removal and
installation” in section 6b .
Remove the throttle cables as shown in the cable routing diagram. Refer
to “thro ...
DTC “c49” (p1656): pair control solenoid
valve circuit malfunction
Detected condition and possible cause
Detected condition
Possible cause
Pair control solenoid valve voltage is not input to ecm
Pair control solenoid valve circuit open or short.
Pair control solenoid valve malfunction.
Ecm malfunction.
...